Control Box Installation Notes
1.) Locate a 7900 Series control box so no more than 100 linear feet of LCN 925 pneumatic tubing is required between the control box and door. Maximum 50 linear feet for a 7980 and 7949 Series.
2.) Locate a 7900/7980/7949 Series control box where the temperatures do not exceed 120°F or fall below 35°F.
3.) 7901, 7902 and 7949 control box input 120V AC @ 1 amp. 7981 and 7982 control boxes input 120V AC @ 5 amp.
4.) Output voltage is 12V DC @ 0.25 amp. max.
5.) Air pressure input, 80 PSI minimum/100 PSI maximum, required for 7901, 7902 and 7949.
6.) Regulated air output up to 80 PSI for Auto Equalizer.
7.) Auto Equalizers require approximately 0.5 cfm airflow in heavy traffic.
8.) All control boxes are 15" x 15" x 6".